<Setting>
• Set the parameters when it is desired to improve the performance in the shortest
acceleration/deceleration mode.
( 1 ) Pr. 61 "reference I for intelligent mode"
Setting
9999 (factory setting)
0 to 500A
( 2 ) Pr. 62 "ref. I for intelligent mode accel"
The reference current setting can be changed.
Setting
9999 (factory setting)
0 to 200%
( 3 ) Pr. 63 "ref. I for intelligent mode decel"
The reference current setting can be changed.
Setting
9999 (factory setting)
0 to 200%
Note: Pr. 61 to Pr. 63 are only valid when any of "1, 2, 11, 12" are selected for
Pr. 60.
Reference Current
Referenced from rated inverter current
Referenced from setting (rated motor current)
Reference Current
150% (180%) is the limit value.
The setting of 0 to 200% is the limit value.
Reference Current
150% (180%) is the limit value.
The setting of 0 to 200% is the limit value.