Mitsubishi FR-E 500 Instruction Manual page 137

Fr-e 500 series transistorized inverter
Hide thumbs Also See for FR-E 500:
Table of Contents

Advertisement

<Setting>
To make communication between the personal computer and inverter, the
communication specifications must be set to the inverter initially. If initial setting is not
made or there is a setting fault, data transfer cannot be made.
Note: After making the initial setting of the parameters, always reset the inverter. After
you have changed the communication-related parameters, communication
cannot be made unit the inverter is reset.
Parameter
Definition
Number
Station
117
number
Communica-
118
tion speed
Stop bit
119
length
Parity check
120
presence/
absence
Number of
121
communication
retries
Communica-
122
tion check
time interval
Waiting time
123
setting
CR⋅LF
instruction
124
presence/
absence
342*
2
E
PROM
(400V
write
class
selection
only)
* When you have set write to RAM, powering off the inverter clears the parameter
values that have been changed. Therefore the parameter values available when
power is switched on again are those stored previously in E
When the parameter values will be changed frequently, set "1" in Pr. 342 to choose
write to RAM.
Setting
Station number specified for communication from the
PU connector.
0 to 31
Set the inverter station numbers when two or more
inverters are connected to one personal computer.
48
4800 bps
96
9600 bps
192
19200 bps
0 Stop bit length 1 bit
8 data
bits
1 Stop bit length 2 bits
10 Stop bit length 1 bit
7 bits
11 Stop bit length 2 bits
0
Absent
1
Odd parity present
Even parity present
2
Set the permissible number of retries at occurrence of
a data receive error.
0 to 10
If the number of consecutive errors exceeds the
permissible value, the inverter will come to an alarm stop.
If a communication error occurs, the inverter will not
come to an alarm stop. At this time, the inverter can be
coasted to a stop by MRS or RESET input.
9999
During a communication error (H0 to H5), the minor
(65535)
fault signal (LF) is switched on. Allocate the used
terminal with any of Pr. 190 to Pr. 192 (multi-function
outputs).
0
No communication
Set the communication check time [seconds] interval.
0.1 to
If a no-communication state persists for longer than the
999.8
permissible time, the inverter will come to an alarm stop.
9999
Communication check suspension
Set the waiting time between data transmission to the
0 to 150
inverter and response.
9999
Set with communication data.
0
Without CR/LF
1
With CR, without LF
2
With CR/LF
When parameter write is performed from
0
computer, parameters are written to E
When parameter write is performed from
1
computer, parameters are written to RAM.
122
PARAMETERS
Description
2
PROM.
2
PROM.
4
the
the