Fire Zone Wiring; Co Detector Wiring; Keypad Zones - DSC PowerSeries PC1404 Installation Manual

V1.0
Hide thumbs Also See for PowerSeries PC1404:
Table of Contents

Advertisement

2.11 Fire Zone Wiring

All 4-wire smoke detectors must be wired according to the fol-
lowing diagram:
All 2-wire smoke detectors must be wired according to the fol-
lowing diagram:

2.12 CO Detector Wiring

POWER
-
PC1404
ZONE
INPUT
-
(SEOL TYPE 41)
RM-1/RM-2
POWER LOOP
SUPERVISORY
RELAY
(12V
, 35mA)
DC
The following CO detector models can be used with PC1404
v1.0 and higher control panels:
Potter Model CO-12/24, UL File E321434
Quantum Model 12-24SIR, UL File E186246
NAPCO Model FW-CO12 or FW-CO1224, UL File
E306780
System Sensor Model CO1224, UL File E307195
CO DETECTOR
ALARM
TROUBLE
+
NC
C
NO NC
C
NO
SEOL
RESISTOR
(5600 ohm)
ALARM
INITIATING
LOOP
RESISTANCE
100 ohm

2.13 Keypad Zones

Each "z" keypad on the system has a zone input to which a
device - such as a door contact - can be connected. This elimi-
nates the need to run wires back to the control panel for every
device.
To install the keypad, open the keypad plastic at the bottom of
the unit. Locate the five terminals on the keypad circuit board.
Connect the four Keybus wires from the control panel: the red
wire to R, the black to B, the yellow to Y and the green to G.
To connect the zone, run one wire to the Z terminal and the other
to B. For powered devices, use red and black to supply power to
the device. Run the red wire to the R (positive) terminal and the
black wire to the B (negative) terminal.
When using end of line supervision, connect the zone according
to one of the configurations outlined in Section 2.9 Zone Wiring.
End of line resistors must be placed on the device end of the
loop, not at the keypad.
Note: Only non 24-hr burglary zones can be configured as key-
pad zones for UL Listed products.
Assigning Keypad Zones
When using keypad zone inputs, each input used must be
assigned a zone number in Installer Programming.
1.
Ensure that you have enrolled all installed keypads into the
desired slots. (See Section 2.6 Keypad Assignment.)
2.
Enter [*][8] [Installer Code] to go to Installer Program-
ming.
3.
Enter Section [20] for Keypad Programming. There are
eight programming locations in this section, one for each
keypad slot.
4.
Enter a 2-digit number (01-08) to specify which zone num-
ber should be assigned to the keypad slot. This number
must be entered in the location corresponding to the keypad
to which each zone is connected.
Example: The zone on an PK5500 keypad in Slot 8 is to be
assigned Zone 3. In Section [020], scroll to Option [8] and enter
(03).
Note: Keypad Zones 1-4 will replace Zone terminals Z1-Z4 on
the control panel.
Note: Once the keypad zones are assigned, you must also pro-
gram zone definitions and zone attributes. (See also 5.2 Pro-
gramming Worksheets).
Note: Keypad zones can only be used for household burglary-
initiated devices. Do not place the device more than 3 feet from
the keypad. The keypad zone must be tested weekly.
2 Installation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents