DSC PowerSeries PC1404 Installation Manual page 61

V1.0
Hide thumbs Also See for PowerSeries PC1404:
Table of Contents

Advertisement

The following attributes are available for the System Trouble PGM Option [09].
System Trouble PGM (Type 09)
[1] Service Required
[2] A.C. Failure
[3] Telephone Line Fault
[4] Communications (Failure to Communicate)
[5] Device (Fire) Fault / WLS Zone Supervisory Fault Enabled
[6] Device Tamper—hardwired or wireless device
[7] Device Low Battery—wireless device
[8] Loss of Clock
The following attributes are available for the System Event PGM Option [10]
System Event PGM (Type 10)
[1] Burglary
[2] Fire
[3] Panic
[4] Medical
[5] Supervisory
[6] Priority
[7] Hold-up
[8] Output Options
If a system event PGM is programmed to follow the command output timer (Attribute 8 On), all other PGM attributes must
i
be enabled.
[551-564] Extended PGM Attributes for PGM Type 29, Zone Follower [551]-[564]
The following attributes are available for the Zone Follower PGM Option [29]:
[1]-[2] Future Use
[3] Output level
[4]-[7] Future Use
[8] Priority
The following attributes are programmable in Installer Sections [551-[564]. Depending on which PGM is used for zone follower
(Onboard, PC5208 or PC5204), the attributes need to be changed in the appropriate section.
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
[601] Closing by Master Code
When the system is armed, a closing reporting code is transmitted after the exit delay expires for the master code that armed the system.
This reporting code is sent to the Opening & Closing call direction group of the system. In addition, either "Armed in Stay Mode" or
"Armed in Away Mode" is logged to the event buffer.
[605] Opening by Master Code
When the system is disarmed, an opening Reporting code for the Master code is transmitted. These reporting codes are sent to the
Opening and Closing call direction group.
Delay, Instant, Interior, Stay/Away, Night, and 24 Hour Burglary Zone Types
Key, Fire zone
Key and Panic zones
Key, Medical, and Emergency zones
Supervisory, Freeze, and Water zones
Gas, Sprinkler, CO, 24-Hour Heat and 24-Hour non-Latching Tamper zones
Duress alarms
ON: Output Follows PGM Timer (Attribute 8). The output activates for the duration pro-
grammed for the PGM output timer (Section [170]).
OFF: Output is latched. The output is active until a valid access code is entered.
ON: Output energizes when activated
OFF: Output de-energizes when activated
ON: AND Logic
OFF: OR Logic
ON: Zone 1 Enabled for Zone Follower
OFF: Zone 1 Disabled for Zone Follower
ON: Zone 2 Enabled for Zone Follower
OFF: Zone 2 Disabled for Zone Follower
ON: Zone 3 Enabled for Zone Follower
OFF: Zone 3 Disabled for Zone Follower
ON: Zone 4 Enabled for Zone Follower
OFF: Zone 4 Disabled for Zone Follower
ON: Zone 5 Enabled for Zone Follower
OFF: Zone 5 Disabled for Zone Follower
ON: Zone 6 Enabled for Zone Follower
OFF: Zone 6 Disabled for Zone Follower
ON: Zone 7 Enabled for Zone Follower
OFF: Zone 7 Disabled for Zone Follower
ON: Zone 8 Enabled for Zone Follower
OFF: Zone 8 Disabled for Zone Follower
5.3 Programming Descriptions