DSC PowerSeries PC1404 Installation Manual page 56

V1.0
Hide thumbs Also See for PowerSeries PC1404:
Table of Contents

Advertisement

PC1404
[348] Test Transmission Reporting Codes
Walk Test Begin/End
These reporting codes are sent when the walk test is initiated and terminated. These codes precede and terminate the alarm reporting
codes for the zones that are activated during the walk test period, if the alarms are to be transmitted (Section [382] Option [2]). The
walk test reporting codes are sent to the System Test Transmission call direction group.
Periodic Test Transmission
When the programmed interval and time of day have elapsed, this reporting code is transmitted. This reporting code is sent to the Sys-
tem Test Transmission call direction group.
System Test
When the [,][6][Master Code][4] command is used to perform a manual system test, this reporting code is sent to test the communica-
tor. This reporting code is sent to the System Test Transmission call direction group.
[350] Communications Format Options
This section requires four 2-digit entries (1 per phone number). See Appendix B: Communicator Format Options.
[351]-[376] Communicator Call Direction Options
Communicator call directions can be configured for 4 different phone numbers. Each reporting code falls under one of the following 5
groups:
Alarms & Restores
Openings & Closings
Tampers & Restores (including System Tampers)
System Maintenance Alarms & Restores
System Test Transmissions
Each group can be assigned to the following call directions:
st
Option 1:
1
Telephone Number
nd
Option 2:
2
Telephone Number
rd
Option 3:
3
Telephone Number
th
Option 4:
4
Telephone Number
[377] Communicator Variables
Program a 3-digit number for each program entry:
Option
Description
[1]
Swinger Shutdown (Alarms): Maximum number of alarm/restore transmissions per zone. Valid entries: [000] to [014]. Pro-
gram data [000] to disable shutdown.
[2]
Swinger Shutdown (Tamper): Maximum number of tamper alarm/restore transmissions per zone. Valid entries: [000] to
[014]. Program data [000] to disable shutdown.
[3]
Swinger Shutdown (Maintenance): Maximum number of trouble alarm/restore transmissions per trouble condition. Valid
entries: [000] to [014]. Program data [000] to disable shutdown.
[4]
Communicator (Transmission) Delay: Time, in seconds, panel delays reporting an alarm event. Valid entries: [000] to
[255].
[5]
AC Failure Communication Delay: Time in minutes or hours that panel delays reporting an AC trouble event or restore.
Valid entries [000] to [255]
Note: AC Restore communications follow the same delay.
[6]
TLM Trouble Delay: Time, in 3 second checks, before the system considers the phone line disconnected. Valid entries:
[003] to [255]
(e.g., 3 x 3 seconds = 9 seconds).
Note: TLM Restore follows the same delay.
[7]
Test Transmission Cycle (Land Line): Number of days between test transmission reporting events. Valid entries: [001] to
[255]. [000] disables the Test Transmission.
[8]
For Future Use

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents