Fire Zone Wiring; 24-Hr Auxiliary Input Wiring (Pgm2); Links Zone Wiring; Keypad Zones - DSC PC5008 Installation Manual

Hide thumbs Also See for PC5008:
Table of Contents

Advertisement

G
E
T
This option should be selected if either Normally
Closed (NC) or Normally Open (NO) detection
devices or contacts are being used .
Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if the
zone is in alarm, tampered or faulted.
To enable panel detection of double end of line resistors,
programming section [013], option [1] must be OFF and option
[2] must be ON.
If the Double EOL supervision option is enabled,
all hardwire zones on the main panel must be
wired for Double EOL resistors, except for Fire
and 24 Hour Supervisory zones.
Do not wire DEOL resistors on keypad zones.
Do not use DEOL resistors for Fire zones or 24
Hour Supervisory zones. Do not wire Fire zones
to keypad zone terminals if the DEOL supervision
option is selected.
This option can only be selected if Normally
Closed (NC) detection devices or contacts are
being used.
Only one NC contact can be connected to each
zone. Wiring multiple detection devices or
contacts on a single loop is not allowed .
The following chart shows zone status under certain conditions:
Loop Resistance
0Ω (shorted wire, loop shorted)
5600Ω (contact closed)
Infinite (broken wire, loop open)
11200Ω (contact open)
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
End of Line Resistors ................................. Section [013]: [1]
Double End of Line Resistors .................... Section [013]: [2]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
2.9

Fire Zone Wiring

4-Wire Smoke Detectors
All fire zones must be wired according to the following diagram:
T
I
N
Loop Status
Fault
Secure
Tamper
Violated
G
S

2.10 24-Hr Auxiliary Input Wiring (PGM2)

If PGM2 has been programmed
for 24-hour operation, the zone
must be wired according to the
following diagram:

2.11 LINKS Zone Wiring

LINKS Support
When using the LINKS 1000
cellular communicator, connect
the LINKS to the main panel
according to the following
diagram:
LINKS Supervision (24 Hour Supervisory)
When using the LINKS 1000 cellular
communicator, any main board
zone may be configured for LINKS
Supervision. Program this zone as
zone type [09], 24 Hour Supervisory
in section [001].
With a LINKS Supervisory zone, if
the LINKS 1000 experiences a
trouble, the zone will be violated,
causing the panel to report the
event to the central station. This
type of zone always requires a
single EOL resistor (5600Ω).
Wire this zone according to the above diagram.
LINKS Answer
When using the LINKS 1000
cellular communicator, any main
board zone may be configured
for LINKS Answer.
A zone configured for LINKS
Answer allows downloading to
be performed in the event of
telephone line failure. When the
LINKS receives a telephone call,
it will activate the RING terminal
on the LINKS circuit board. The
zone programmed as LINKS
Answer always requires a single
EOL resistor (5600Ω).
Wire the LINKS Answer zone according to the above diagram.
The LINKS Answer zone is only required for
downloading to the panel via the LINKS.
When using the LINKS, Busy Tone Detection must
not be used.
Keypad zones cannot be used for 24 Hour
Supervisory or LINKS Answer.