The following information is for general guidance only and it is recommended that local fire codes and regulations be consulted when
locating and installing smoke and CO alarms.
Research indicates that all hostile fires in homes generate smoke to a greater or lesser extent. Detectable quantities of smoke precede
detectable levels of heat in most cases. Smoke alarms should be installed outside of each sleeping area and on each storey of the home.
DSC recommends that additional smoke alarms beyond those required for minimum protection be installed. Additional areas that
should be protected include: the basement; bedrooms, especially where smokers sleep; dining rooms; furnace and utility rooms; and
any hallways not protected by the required units.
On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on ceiling
height, air movement, the presence of joists, uninsulated ceilings, etc. Consult National Fire Alarm Code NFPA 72, CAN/ULC-S553-
02 or other appropriate national standards for installation recommendations.
Do not locate smoke detectors at the top of peaked or gabled ceilings; dead air space in these locations may prevent smoke detec-
tion.
Avoid areas with turbulent air flow, such as near doors, fans or windows. Rapid air movement around the detector may prevent
smoke from entering the unit.
Do not locate detectors in areas of high humidity.
Do not locate detectors in areas where the temperature rises above 38
Smoke detectors should always be installed in accordance with NFPA 72, the National Fire Alarm Code. Smoke detectors should
always be located in accordance with:
"Smoke detectors shall be installed outside of each separate sleeping area in the immediate vicinity of the bedrooms and on each addi-
tional storey of the family living unit, including basements and excluding crawl spaces and unfinished attics. In new construction, a
smoke detector shall also be installed in each sleeping room." Split level arrangement: Smoke detectors are required where shown.
Smoke detectors are optional where a door is not provided between living room and recreation room.
Figure 1
CO gas moves freely in the air. The human body is most vulnerable to the effects of CO gas during
sleeping hours. For maximum protection, a CO alarm should be located outside primary sleeping
areas or on each level of your home. Figure 5 indicates the suggested locations in the home. The
electronic sensor detects carbon monoxide, measures the concentration and sounds a loud alarm
before a potentially harmful level is reached.
Do NOT place the CO alarm in the following areas:
Where the temperature may drop below -10ºC or exceed 40 ºC.
Near paint thinner fumes.
Within 5 feet (1.5 meters) of open flame appliances such as furnaces, stoves and fireplaces.
In exhaust streams from gas engines, vents, flues or chimneys.
Do not place in close proximity to an automobile exhaust pipe; this will damage the detector.
Figure 2
Figure 3a
o
o
o
C (100
F) or falls below 5
C (41
Figure 3
Figure 4
BEDROOM
GROUND
FLOOR
BASEMENT
CARBON MONOXIDE DETECTOR
o
F).
BEDROOM
BEDROOM
GARAGE
KITCHEN
Figure 5