UPS Installation Plan and Unpacking
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load. The recommended line-to-line load unbalance is 50% or less with reference to
full load.
Readily accessible disconnect devices (Bypass and output overcurrent protection and bypass and output
disconnect switches) are to be supplied by the customer. Table 3-8 lists the Recommended Bypass Circuit
Breaker, Output Circuit Breaker and Bypass Fuse Ratings.
Table 3-8. Recommended Bypass Circuit Breaker, Output Circuit Breaker and Bypass Fuse Ratings
93E MK2-10I-9Ah-MBS
93E MK2-15I-9Ah-MBS
93E MK2-20I-9Ah-MBS
93E MK2-30I-9Ah-MBS
93E MK2-40I-9Ah-MBS
If internal battery option used, UPS default with DC disconnect device by factory default
If external battery option used,
battery location is to be provided by the user. Table 3-9 lists the maximum rating for continuous-duty rated circuit
breakers satisfying the criteria for both.

Table 3-9. Recommended DC input circuit breaker rating

16
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table 3-7 in accordance with local regulations.
Load Derating
UPS Model
80% Derating
100% Rating
80% Derating
100% Rating
80% Derating
100% Rating
80% Derating
100% Rating
80% Derating
100% Rating
External DC input overcurrent protection and disconnect switch for the remote
Circuit Breaker Rating
UPS Model
93E MK2-10I-9Ah-MBS
93E MK2-15I-9Ah-MBS
93E MK2-20I-9Ah-MBS
93E MK2-30I-9Ah-MBS
93E MK2-40I-9Ah-MBS
Eaton 93E MK2 UPS (10-40kVA, 380/400/415V) Installation and Operation
CAUTION
Circuit Breaker Rating
400V
18A
14A
27A
22A
36A
29A
54A
43A
72A
58A
Load Derating
80% Derating
100% Rating
80% Derating
100% Rating
80% Derating
100% Rating
80% Derating
100% Rating
80% Derating
100% Rating
Fuse Parameters
Current/Min
I2T/Max
20A
10200A
32A
10200A
40A
10200A
63A
10200A
80A
20,400 A
Bat rated voltage(DC432V)
23A
34A
46A
69A
92A
2
Sec
2
Sec
2
Sec
2
Sec
2
Sec