Serial Rs485 Communication Connector - Toshiba TOSVERT VF-AS1 Instruction Manual

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

2.3.3 Serial RS485 communication connector

The VF-AS1 is equipped with two connectors: a two-wire RS485 connector (on the operation panel) and a four-wire
RS485 connector. The two wire RS485 connector is used to connect an external option (such as remote keypad or
computer) to the inverter. To connect to a network, use the four-wire RS485 connector, following the instructions
below.
2
2-wire RS485
Signal
Pin
name
number
DA
DB
SG
This table shows signal line of inverter side.
* Never use pin-1, 2, 3, 6 and 7.
Connecting diagram for 4-wire RS485 communication
Upper computer or
VF-AS1 (master)
Note
* Separate the communication line and the main circuit wiring by 20cm or more.
* Never use pin-1 (P24) and pin-7 (P11).
* Connect RXA and RXB, between TXA and TXB using twisted pair cable.
* Connect terminating resistances at both ends of a transmission line.
* When using 2-wire type, short RXB to TXB and RXA to TXA.
When connecting a communications device via the two-wire connector, carefully read the precautions for use in the
operating manual for the communications device.
* When connecting the VF-AS1 to other inverters, you do not need to connect the master receive lines (pins 4 and 5)
or the slave send lines (pins 3 and 6).
Pin-1
Pin-8
Description
4
Same phase data
5
Anti-phase data
8
Ground line of signal data
cross each other
AS1 (slave)
RXA
RXA
RXB
RXB
TXA
TXA
TXB
TXB
SG
SG
4-wire RS485
Signal
Pin
name
number
RXA
4
Same phase reception data (positive line)
RXB
5
Anti-phase reception data (positive line)
TXA
3
Same phase transmitting data (positive line)
TXB
6
Anti-phase transmitting data (positive line)
SG
2, 8
Ground line of signal data
This table shows signal line of inverter side.
(Example: RXA signal is received by inverter.)
* Never use pin-1 (P24) and pin-7 (P11).
straight
AS1 (slave)
RXA
RXB
TXA
TXB
SG
B-16
E6581445
2-wire RS485 communication
4-wire RS485 communication
Description
straight
AS1 (slave)
RXA
RXB
TXA
TXB
SG
Terminating
resistance
100Ω
-1/4W

Advertisement

Table of Contents
loading

Table of Contents