Simplified Operation Of The Vf-As1; Terminal Board Operation - Toshiba TOSVERT VF-AS1 Instruction Manual

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

3.2

Simplified operation of the VF-AS1

On of three operation modes can be selected: terminal board operation, operation panel and combination of both.
⇒ For other operation modes, refer to Section 5.5.
Terminal board mode
Operation panel mode
Operation panel + terminal board mode

3.2.1 Terminal board operation

In this mode, the motor is started or stopped according to the ON/OFF signal to input terminals (such as the ST
terminal and the F terminal). Also, the frequency is set according to the potentiometer/voltage/current signals to analog
input terminals (such as the RR/S4 terminal, VI/II terminal and RX terminal).
⇒ For more details, refer to Section 7.
Example of standard connection
MCCB
Power
supply
Run/Deceleration stop Selecting a command mode for basic parameters = (standard default setting)
F
are connected: Forward run
CC
and
F
CC
are disconnected: Deceleration stop
and
(When terminals
ST
Frequency
F-CC
ST-CC
:Operation by means of external signals
:Operation by pressing keys on the operation panel
sent individually from the operating panel and terminal board.
R/L1
S/L2
T/L3
Inverter
RX VI/II RR/S4 PP
CCA
External potentiometer (or voltage signal RR/S4-CCA:0 to 10V)
and
are electrically connected)
CC
Deceleration
C-3
:Frequency, start/stop signals can be
Motor
U/T1
IM
V/T2
W/T3
F
ON:Forward run, OFF:Deceleration stop
R
ON:Reverse run, OFF:Deceleration stop
ST
Stand-by:ON:Stand-by, OFF:Coast stop
CC
Voltage signal:-10~+10Vdc
Voltage signal:0~10Vdc
or current signal:4(0)~20mAdc
For coast stop
Open the connection between ST and CC
when stopping the motor in the state
described at left. The monitor on the inverter
at this time will display .
Motor
speed
F-CC
ON
OFF
ST-CC
ON
OFF
E6581445
3
Coast stop
ON
OFF
ON
OFF

Advertisement

Table of Contents
loading

Table of Contents