Toshiba TOSVERT VF-AS1 Instruction Manual page 255

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

[4] Terminal response time setup
Communi
Title
cation
Function
No.
Input terminal 1 response time

0140
selection (F)
Input terminal 2 response time

0141
selection (R)
Input terminal 3 response time
0142

selection (ST)
Input terminal 4 response time
0143

selection (RES)
Input terminal 5~12 response

0144
time selection
Input terminal 13~20 response

0145
time selection

0164
Input terminal selection 17(B12) 0~135 *1
0165
Input terminal selection 18(B13) 0~135 *1


0166
Input terminal selection 19(B14) 0~135 *1
0167
Input terminal selection 20(B15) 0~135 *1

Output terminal function
0168

selection 10 (R3) *4
Output terminal function
0169

selection 11 (R4) *4

0170
Base frequency 2

0171
Base frequency voltage 2

0172
Manual torque boost 2

0173
Thermal protection level 2

0174
Base frequency 3

0175
Base frequency voltage 3

0176
Manual torque boost 3

0177
Thermal protection level 3

0178
Base frequency 4

0179
Base frequency voltage 4

0180
Manual torque boost 4

0181
Thermal protection level 4
*1: ⇒ For the adjustment range, see the table on page K-41.
*2: ⇒ For the adjustment range, see the table on page K-43.
*3: Default values vary depending on the capacity. ⇒ See the table of K-46.
*4: Unsupported option
Adjustment range
2~200ms
2~200ms
2~200ms
2~200ms
2~200ms
5~200ms
0~255 *2
0~255 *2
25.0~ Hz
50~330V/660V
0.0~30.0%
10~100%
25.0~ Hz
50~330V/660V
0.0~30.0%
10~100%
25.0~ Hz
50~330V/660V
0.0~30.0%
10~100%
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
(Panel/Communi
setting
running
control
cation)
1/1
8
Disabled
●/●
1/1
8
Disabled
●/●
1/1
8
Disabled
●/●
1/1
8
Disabled
●/●
1/1
8
Disabled
●/●
1/1
8
Disabled
●/●
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
1/1
254
Disabled
●/●
1/1
254
Disabled
●/●
0.1/0.01
60.0
Disabled
-
1/0.1
*3
Disabled
-
0.1/0.1
*3
Enabled
-
1/1
100
Enabled
-
0.1/0.01
60.0
Disabled
-
1/0.1
*3
Disabled
-
0.1/0.1
*3
Enabled
-
1/1
100
Enabled
-
0.1/0.01
60.0
Disabled
-
1/0.1
*3
Disabled
-
0.1/0.1
*3
Enabled
-
1/1
100
Enabled
-
PM
Torque
V/f
Reference
control
control
●/●
7. 2. 3
●/●
7. 2. 3
●/●
7. 2. 3
●/●
7. 2. 3
●/●
7. 2. 3
●/●
7. 2. 3
●/●
7. 2. 1
●/●
7. 2. 1
●/●
7. 2. 1
●/●
7. 2. 1
●/●
7. 2. 2
●/●
7. 2. 2
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1
-
-
6. 4. 1