8.2.2 Display of detailed information on a past trip

Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the
trip record is selected in the status monitor mode.
Unlike the " Monitor display at tripping " in 8.4.2, details on a past trip can be displayed, even after the inverter is turned off
or reset.
Item displayed
[Note 5]
Past trip 1
Continuous trips
[Note 1]
Output frequency
Status monitor mode
(Rotating direction)
Frequency command
value
Output current
[Note 2]
[Note 2]
Input voltage (DC
[Note 3]
detection)
Output voltage
[Note 2]
Input terminal
information
Output terminal
[Note 4]
information
Cumulative operation
[Note 6]
time
Past trip 1
Note 1: Press the
Note 2: You can switch between % and A (ampere)/V (volt), using the parameter  (current/voltage unit selection).
Note 3: The input voltage displayed is 1/ 2 times as large as the rectified DC input voltage.
Note 4: The number of bars displayed varies depending on the setting of  (logic output/pulse train output
selection). The bar representing the OUT1 terminal is displayed only when logic output function is assigned to it.
If =
If =
Note 5: If there is no trip record,  is displayed.
Note 6: The cumulative operation time increments only when the machine is in operation.
Key
LED display
operated
 ⇔  Past trip 1 (displayed alternately.)
The number of time the same trip occurred in succession is displayed.
ENT

(, , ,  Unit: times)
The operation frequency when the trip occurred is displayed.

The direction of rotation is displayed. (:Forward run, :Reverse run)

The operation frequency command value is displayed.

(When =, Frequency command)
The inverter output current (load current) is displayed.

(When =, Output current)
The inverter DC voltage is displayed. (Default setting unit: %)

(When =, Input voltage) [Note 3]
The inverter output voltage is displayed. (Default setting unit: %)

(When =, output voltage)
The ON/OFF status of each of the control signal input terminals (F, R,
    
ST, RES, S1, S2, S3, RR/S4) is displayed in bits.
The ON/OFF status of each of the control signal output terminals
  
(OUT1, OUT2, FL) is displayed in bits.
The cumulative operation time when the trip occurred is displayed.

(0.01=1 hour, 1.00=100 hours)
 ⇔ 
Press this key to return to past trip 1.
MODE
or
key to change items displayed in the status monitor mode.
:The bar representing OUT1 is displayed.
:The bar representing OUT1 is not displayed.
H-5
E6581445
key when the
ENT
Description