Toshiba TOSVERT VF-AS1 Instruction Manual page 160

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

For a crane/hoist, an elevator application, as lifted
up and down at controlled speeds, the direction of
rotation is frequently reversed. In such cases, the
load can be started smoothly, by adding load
torque into the torque reference equivalent to the
additional torque, when starting acceleration after
releasing the brake.
[Selection of external signals]
Voltage signals
Current signals
2) Selection of tension torque bias input and load sharing gain input
Load sharing gain
Torque reference
6
Tension torque bias
[Parameter setting]
Title




[Selection of external signals]
Voltage signals
Current signals
RR/S4-CCA – 0~10V
RX-CCA – 0~±10V
VI/II-CCA – 0~10V
VI/II-CCA – 4(0)~20mA
Function
Tension torque bias input
selection
Control panel tension torque bias
Load sharing gain selection
Control panel load sharing gain
RR/S4-CCA – 0~10V
RX-CCA – 0~±10V
VI/II-CCA – 0~10V
VI/II-CCA – 4(0)20m
Tension torque bias
as additional torque
Additional torque
(fixed direction)

(0~250%)
(-250~250%)
(0~250%)
(0~250%)
+
×
+
+
Adjustment range
:Disabled
:VI/II (voltage/current input)
:RR/S4 (potentiometer/voltage input)
:RX (voltage input)
:Operation panel input enabled (including
LED/LCD option input)
:2-wire RS485 input enabled
:4-wire RS485 input enabled
:Communication option input enabled
:Optional AI1 (Differential current input)
~ %
:Disabled
:VI/II (voltage/current input)
:RR/S4 (potentiometer/voltage input)
:RX (voltage input)
:Operation panel input enabled (including
LED/LCD option input)
:2-wire RS485 input enabled
:4-wire RS485 input enabled
:Communication option input enabled
:Optional AI1 (Differential current input)
~ %
, 
(0~250%)
(-250~250%)
(0~250%)
(0~250%)
F-44
E6581445
Reverse run
Forward run
Torque command
Default setting
