 : Baud rate
 : Parity
 : Inverter number
 : Communication time-out time
 : Communication time-out action
 : Communication waiting time
 : Communication time-out
 : Selection of communication
 Set the parameter Communication time-out time (f803) and Communication time-out action (f804).
6
If these are not properly set, the inverter cannot be stopped immediately in breaking communication and
this could result in injury and accidents.
 An emergency stop device and the interlock that fit with system specifications must be installed.
Mandatory
If these are not properly installed, the inverter cannot be stopped immediately and this could result in
action
injury and accidents.
Refer to the Communications Function Instruction Manual (E6581657) for details.
 Function
2-wire RS485 communication is built-in as standard.
Connect with the host to create a network for transmitting data between multiple inverters. A computer
link function is available.
<Computer-linking functions>
 Timer function
 Broadcast communication function
 2-wire RS485 communication option is as follows.
(1) USB communication exchange unit (Type: USB001Z)
Cable for communication between the inverter and the unit (Type: CAB0011 (1m), CAB0013 (3m),
CAB0015 (5m))
Cable for communication between the unit and computer: Use a commercially available USB 1.1 or 2.0
cables. (Type: A-B, Cable length: 0.25 to 1.5m)
detection condition
protocol
The following functions are enabled by data communication between the computer and inverter
(1) Monitoring inverter status (such as the output frequency, current, and voltage)
(2) Sending RUN, STOP and other control commands to the inverter
(3) Reading, editing and writing inverter parameter settings
 : Block write data 1
 : Block write data 2
 : Block read data 1
 : Block read data 2
 : Block read data 3
 : Block read data 4
 : Block read data 5
Warning
...Function used to detect cable interruptions during communication.
When data is not sent even once to the inverter during a user-
defined period of time, an inverter trip ( is displayed on the
panel) or an output terminal alarm can be output.
...Function used to send a command (data write) to multiple
inverters with a single communication.
F-62
E6581595