Toshiba TOSVERT VF-AS1 Instruction Manual page 79

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

2) Setting the run and stop frequencies (forward run, reverse run and coast
stop) by means of external signals and setting the operation frequency
with the operation panel
Title
Function

Command mode selection

Frequency setting mode
selection 1
R/L1
Power
S/L2
supply
T/L3
Inverter
CCA RX VI/II RR/S4 PP
3) Setting the run and stop frequencies (forward run, reverse run and
deceleration stop) with the operation panel and setting the operation
frequency by means of external signals
Title
Function
Command mode

selection
Frequency setting

mode selection 1
R/L1
Power
S/L2
supply
T/L3
Inverter
CCA RX VI/II RR/S4 PP
(2) External potentiometer
Example of setting
 (Terminal
input)
 (Operation
panel input)
Motor
U/T1
IM
V/T2
W/T3
ON:Forward run,
F
OFF:Deceleration stop
ON:Reverse run,
R
OFF:Deceleration stop
ON:Standby,
ST
OFF:Coast stop
CC
Example of setting
 (Operation panel input)
(VI/II (voltage/current
input) )
(RR/S4 (potentiometer/
(1) VI/II terminal: 0~+10Vdc
voltage input) )
(RX (voltage input) )
(2) RR/S4 terminal: Potentiometer
(3) RX terminal: 0~±10Vdc (0~±5Vdc)
Motor
U/T1
IM
V/T2
W/T3
F
R
ST
Shorted by a shorting bar when
shipped from the factory.
CC
+
(3) 0~±10Vdc
-
(0~±5Vdc)
(1) 0~+10Vdc
+
-
(0~+5Vdc)
or 4(0)-20mA
E-9
Run/stop : ON/OFF of terminals F-CC/R-CC
(Standby: connection of terminals
ST and CC)
Speed command : Set the frequency, using
the
the operation panel.
The inverter is factory-
configured so that, if F and
R are turned on at the
same time, the inverter will
stop operation. If
necessary, the direction of
rotation can be reversed
by changing parameter
settings.
⇒ Refer to Section 6.2.1.
To save the frequency,
press the ENTER key.
Then,  and the set
frequency are
displayed alternately
for a while.
Run/stop : Press the
RUN
and
the operation panel
To switch between forward run and reverse run,
use the forward/reverse run selection .
Speed command : External signal input
(0~+5Vdc) or
4(0)~20mAdc
0~+10Vdc (0~+5Vdc)
* Other speed setting
: 2-wire RS485 input
: 4-wire RS485 input enabled
: Communication option input
enabled *
: Optional AI1 (differential current
input) *
: Optional AI2 (voltage/current
input) *
: Up/Down frequency
: RP pulse input *
: High-speed pulse input *
: -
* Commands marked with * are
optional. Refer to Instruction Manual
of options described in Section 10.
E6581445
keys on
5
STOP
keys on