Toshiba TOSVERT VF-AS1 Instruction Manual page 260

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

[12] Tripless intensification setup [2/2]
Communi
Title
cation
Function
No.
0304
Dynamic braking selection


0305
Overvoltage limit operation
Base frequency voltage
0307
selection

(correction of supply voltage)

0308
Dynamic braking resistance

0309
Allowable continuous braking resistance 0.01~600.0kW
Non-stop control time/deceleration

0310
time during power failure
Reverse-run prohibition

0311
selection

0312
Random mode
Carrier frequency control mode

0316
selection
Synchronized deceleration time
0317
(time elapsed between start of

deceleration to stop)
Synchronized acceleration time
(time elapsed between start of

0318
acceleration to achievement of
specified speed)
Regenerative over-excitation
0319

upper limit
This parameter moves to a fundamental parameter. *1: Default values vary depending on the capacity. ⇒ See the table of K-46.
*2: Changing the parameter  enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
*3: Although the setting can be written into memory if  is set to  (power ride-through control), it cannot be written if  is set to  (deceleration stop during a power failure).
[13] Drooping control
Communi
Title
cation
Function
No.

0320
Drooping gain

0321
Speed at drooping gain 0%

0322
Speed at drooping gain  0.0~320.0Hz (Enabled if =3, 4, 7 or 8)

0323
Drooping insensitive torque
*1: Drooping gain can be changed within a range of 0.1 to 100.0% during operation. When changing the setting to 0.0 (no drooping) or 0.0, stop operation.
Adjustment range
0:Disabled
1:Enabled (braking resistance overload detect)
2:Enabled (braking resistance overload not detect)
0:Enabled
1:Disabled
2:Enabled (quick deceleration)
3:Enabled (dynamic quick deceleration)
0:Without voltage compensation (limitless output voltage)
1:With voltage compensation (limitless output voltage)
2:Without voltage compensation (limited output voltage)
3:With voltage compensation (limited output voltage)
0.5~1000Ω
0.1~320.0 sec.
0:Permit all, 1:Prohibit reverse run
2:Prohibit forward run
0:Disabled, 1:Enabled
0:Not decrease carrier frequency automatically
1:Decrease carrier frequency automatically
2:Not decrease carrier frequency automatically,
400V class supported
3:Decrease carrier frequency automatically, 400V
class supported
0.1~6000 sec.
0.1~6000 sec.
100~160%
Adjustment range
0.0~100.0% (Enabled if =3, 4, 7 or 8)
0.0~320.0Hz (Enabled if =3, 4, 7 or 8)
0~100% (Enabled if =3, 4, 7 or 8)
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
(Panel/Communi
setting
running
control
cation)
1/1
0
Disabled
●/●
1/1
2
Disabled
●/●
Parameter is changeable, but fixed to
"with voltage compensation" internally.
When  is set to 0 or 1, fixed at
1/1
1
Disabled
1 internally.
When  is set to 2 or 3, fixed at
3 internally.
0.1/0.1
*1
Disabled
●/●
0.01/0.01
*1
Disabled
●/●
Enabled *3/
0.1/0.1
2.0
●/●
Disabled
1/1
0
Disabled
●/●
1/1
0
Disabled
●/●
1/1
1
Disabled
●/●
0.1/0.1 *2
2.0
Enabled
●/●
0.1/0.1 *2
2.0
Enabled
●/●
1/1
140
Disabled
●/●
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Minimum
Vector control
setting unit
Default
Write during
Speed
(Panel/Communi
setting
running
control
cation)
0.1/0.1
0.0
Enabled *1
●/●
0.1/0.01
0.0
Enabled
●/●
0.1/0.01
0.0
Enabled
●/●
1/1
10
Enabled
●/●
PM
Torque
V/f
Reference
control
control
●/●
5. 19
●/●
6. 14. 2
6. 14. 3
●/●
5. 19
●/●
5. 19
-/-
5. 18. 2
●/●
6. 14. 4
●/●
5. 17
●/●
5. 17
-/-
5. 18. 2
-/-
5. 18. 2
●/●
-
6. 14. 2
PM
Torque
V/f
Reference
control
control
-
-
-
6. 15
-
-
-
6. 15
-
-
-
6. 15
-
-
-
6. 15

Advertisement

Table of Contents
loading

Table of Contents