Using This Section; Specifications For All Function Blocks - Omron G9SP Series Reference Manual

Safety controller
Hide thumbs Also See for G9SP Series:
Table of Contents

Advertisement

Using this Section

3-1
Using this Section
Item
Instruction Name
Overview
Diagram
General Description
Parameter Settings
Optional I/O Settings
Truth Tables
Error Handling and Error
Resetting
Timing Charts
3-2

Specifications for All Function Blocks

12
The following items are described for each function block.
The name of the function block is given.
Example: Emergency Stop Switch Monitoring
An overview of the function block functions is provided.
The Logic Editor symbol is shown.
Example:
The functions of the function block are described in detail.
Example: Emergency Stop Switch Monitoring
When an input from the Emergency Stop Switch is activated, the Output Enable signal is
turned ON. When an input is not activated or when an error is detected in the function block,
the Output Enable signal is turned OFF.
The parameters to be set for the function block are described.
Example:
Parameter
Input Type
• Single Channel
• Dual Channel Equivalent
• Dual Channel Complementary
Discrepancy Time
0 to 30 s in units of 10 ms
Discrepancy time checks are not
performed when this parameter is
set to 0.
The additional I/O signals that can be set are described.
The output signals corresponding to combinations of input signals are given.
Error status, operations when an error occur, and the recovery procedure are given.
I/O operations are shown in timing charts.
Function blocks can be edited according to the application by setting parame-
ters and adding optional inputs, optional outputs, and comments. The tabs
displayed and the settings depend on the function block. This section gives
specifications that are the same for all function blocks.
Contents
Setting range
Section 3-1
Default
Dual Channel Equiva-
lent
30 ms