Power for Pure Metal Heater, and Incorporates Overcurrent Detecting and Single Heater Burnout Detecting Functions OMRON’s unique design and carefully-selected materials made it possible to produce a compact and lightweight Power Controller. Replaceable, easy-to-install Power Device Car- tridge assures ease of maintenance.
Page 2
(see note 1) detection detection 100/110 VAC 00/ 0 Single Resistive load 20 A G3PX-220EH-CT03 Heater G3PX-220EH-CT10 200/230 VAC 200/230 VAC (see note 3) 40 A G3PX-240EH-CT03 G3PX-240EH-CT10 60 A G3PX-260EH-CT03 G3PX-260EH-CT10 Yes (see note 2) 20 A...
G3PX G3PX Specifications Ratings Control Item G3PX- G3PX- G3PX- G3PX- 220EUN/ 220EH/ 220EHN/ 220EC/ 240EUN/ 240EH/ 240EHN/ 240EC/ 260EUN 260EH 260EHN 260EC Rated voltage 100/110, 200/230 VAC Frequency 50/60 Hz (see note 1) Input External 2 kΩ (type B, 2 W min.) 3 kΩ...
Page 4
G3PX G3PX Item G3PX-220EUN/ G3PX-220EH/240EH/260EH G3PX-220EHN/ 240EUN/260EUN 240EHN/260EHN π Min. phase detection Approx. 1/6 π Min. phase setting Approx. 1/6 Min. load current for 30% max. of rated current ON error detecting (see note 5) Abnormality detection 0.1 s max. 1 s max.
G3PX G3PX Engineering Data The following data is for an ambient temperature of 25 C. Output Characteristics Duty Setting G3PX-EUN/EH/EHN Models G3PX-EC G3PX-EUN/EH/EHN Models 100% Input current (mA) Input current (mA) Input current (mA) Base-up Characteristics G3PX-2 0EUN Models Input current (mA) Load Current vs.
Page 6
G3PX G3PX Withstand Inrush Current G3PX-220E Models G3PX-240E Models G3PX-260E Models Energizing time (ms) Energizing time (ms) Energizing time (ms) Note: The above are possible on condition that the G3PX is in non-repetitive operation. If the G3PX is in repetitive operation, reduce the applied current to half.
Page 7
G3PX G3PX Nomenclature Single-function Model Multiple Heater Burnout Detection (EUN-series Model) (EHN-series Model) G3PX-2 0EUN G3PX-2 0EHN-CT RUN/SET switch for setting condition for multiple heater burnout detection. Level indicator Level indicator RESET switch POWER indicator POWER indicator SHORT indicator (for short-mode BASE-UP adjuster failure detection) DUTY adjuster...
G3PX G3PX Operation Error Detecting Function Wiring Single-phase Models 2. When EH/EHN/EC-series models detect a short-mode failure, the SHORT indicator is lit and the SPDT relay output is All G3PX-2 0EH/EHN/EC-series models incorporate terminals 11 and 12 for the CT Unit, 13 and 14 for the external reset switch, and 16 and 17 for relay output as well as power/input terminals 1 through With continuous load current.
Page 9
*Impedance Load 2 Note: Two G3PX models can be connected in series to OMRON’s single Tempera- ture Controller (with an internal impedance of 600 Ω) with a current output. 2. A Temperature Controller with an output of 7 to 20 mA is used with the G3PX to change the duty.
Page 10
G3PX G3PX ON/OFF Control Single-phase Models 1. A Temperature Controller is used to change the duty of G3PZ. Load 1 Internal DUTY adjuster 5/12/24 VDC E5 S Tem- ON/OFF perature Controller – G3PX DUTY Load 2 G32X-V3K External DUTY Adjuster (3 kΩ) Note: You can change the duty with the external or internal variable resistor.
Page 11
G3PX G3PX Manual Control Single-phase Models Load 1 G32X-V3K or G32X-V2K External DUTY Adjuster Internal DUTY adjuster Note: Delicate duty adjustment is possi- ble with the external or internal re- sistor. G3PX G32X-V3K External DUTY Use a right DUTY adjuster (2- or Adjuster (3 kΩ) for duty set- 3-kΩ...
Page 12
G3PX G3PX 4. Set the RUN/SET switch to RUN. When all settings have been finished, the OPEN indicator is OFF. Note: 1. The G3PX can control any part of the phase as long as π the controlled phase is approximately 1/6 or more in width.
G3PX G3PX Replacement Parts G32X-A Power Device Cartridge The temperature indicator will be lit in red if the power element is damaged. If the power element is damaged due to overcurrent or other rea- sons, the power element and its peripheral parts can be replaced. The power element and its peripheral parts can be replaced without disconnecting the wires of the G3PX.
Page 14
G3PX G3PX 4. Loosen the screws on both corners. 3. Insert the Cartridge into the opening of the G3PX so that the letters on the Cartridge and those on the G3PX are in the same direction and sides A and B are even. Loosen Loosen 5.
Page 15
G3PX G3PX Dimensions Note: All units are in millimeters unless otherwise indicated. Single-phase Models G3PX-220E Series Mounting Holes Four, 4.5 dia. or M4 holes 140 0.3 50 0.3 Two, 4.6 dia. Two, M4 screws holes 140 0.2 109.8 150 max. Two, R2.3 holes 50 0.2...
Page 16
G3PX G3PX G3PX-260E Series Mounting Holes Four 4.5-dia. or M4 holes 140 0.3 80 0.3 Two, 4.6 dia. Two, M6 screws holes 140 0.2 109.8 150 max. Two, R2.3 holes 80 0.2 100 max. 130 max. G32X-CT03 Series 60 max. G32X-CT10 Series Mounting Holes...
G3PX G3PX Installation Terminal Arrangement Single-phase Models G3PX-220EUN G3PX-220EH G3PX-240EUN G3PX-240EH G3PX-260EUN G3PX-260EH CT UNIT G32X-CT External main setting 2 kΩB, 2 W for External main setting 3 kΩB 2 W EUN-series models 3 kΩB 2 W MAN SET MAN SET Voltage ON/OFF input Voltage ON/OFF input VOLTAGE IN...
Wiring Only resistive loads can be connected to the G3PX. Contact your Make sure that the lead wires are thick enough according to the cur- OMRON representatives if it is necessary to connect inductive or rent. transformer loads. Be sure to turn off power to the G3PX when wiring. The G3PX has...
Page 19
G3PX G3PX If any of the following models is used and the actual load current is Also check the current limit adjuster if the G3PX is a constant DC 50% of the maximum rated load current or lower, increase the num- model.
Page 20
G3PX G3PX When the supply current is 25% of the rated current, the wires The OPEN indicator of a multiple heater burnout detection model must be coiled three to four times on the CT Unit. is lit at the initial stage (G3PX-2 0EHN Series). No reset will be performed even if the RESET button is pressed.