Connector Function Blocks
Optional Output
Settings
3-7-2
Routing
Basic Function
Diagram
General Description
Optional Output Settings
80
The number of outputs can be increased on the In/Out Setting Tab Page in the
function block property dialog box.
Parameter
Number of I/O
1 to 8
Used for routing an input signal to multiple signals.
Default
The Routing function block routes one input signal to a maximum of eight out-
put signals. It is used to output a signal to more than one output tag.
With an G9SP-series Controller, it is not possible to make a direct connection
from one signal to two output tags. To do so, distribute the signal by using a
Routing function block.
The number of outputs can be increased on the In/Out Setting Tab Page in the
function block property dialog box.
Parameter
Number of outputs
1 to 8
Setting range
Maximum Number of Outputs
Setting range
Section 3-7
Default setting
1
Default setting
1