Specifications for All Function Blocks
Setting: Single Channel
Setting: Dual Channel
Equivalent
Setting: Dual Channel
Complementary
Setting: Dual Channel
Equivalent (2 Pairs)
14
The following truth tables outline the internal evaluations performed by the
G9SP-series Controller for each type of input signal. In the tables, 0 indicates
OFF and 1 indicates ON.
Input 1 (NC)
Output Enable
0
1
Input 1 (NC)
Input 2 (NC)
0
0
1
1
Input 1 (NC)
Input 2 (NO)
0
0
1
1
Input 1 (NC)
Input 2 (NC)
0
0
0
0
0
0
0
0
0
1
0
1
0
1
0
1
1
0
1
0
1
0
1
0
1
1
1
1
1
1
1
1
0
1
Output Enable
0
0
1
0
0
0
1
1
Output Enable
0
0
1
0
0
1
1
0
Input 3 (NC)
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
Section 3-2
Input 4 (NC)
Output Enable
0
0
1
0
0
0
1
0
0
0
1
0
0
0
1
0
0
0
1
0
0
0
1
0
0
0
1
0
0
0
1
0

Hide quick links: