Replacing The Hot-Plug Fan Modules - Fujitsu PRIMERGY RX300 S6 Operating Manual

Hide thumbs Also See for PRIMERGY RX300 S6:
Table of Contents

Advertisement

8.1.3

Replacing the hot-plug fan modules

V
CAUTION!
Please observe the safety information in
information" on page
In order to replace a defective fan, it is necessary to remove the housing cover,
because the fans are not directly accessible (see
housing" on page
V
CAUTION!
The housing cover must be replaced as soon as possible for purposes of
cooling, to comply with EMC regulations (regulations regarding
electromagnetic compatibility) and to prevent fires. The housing cover
must not remain open for longer than 5 minutes.
I
The PRIMERGY RX300 S6 server with a 48 V DC power supply is
equipped with 10 fans. Do not remove one fan without replacing it.
The server is equipped with five separate hot-plug fan modules. The redundant
fan configuration allows one fan to fail and the system still works. To ensure the
redundancy of the fan system the faulty fan has to be replaced immediately.
A predicted fan fault is reported by the Global Error indicator lighting up on the
front and rear of the server. When the housing cover is open, the faulty fan can
be identified by the corresponding LED
replaced while the system is running.
To ensure the redundancy of the fan system the faulty fan has to be replaced
immediately.
RX300 S6
31.
119).
Operating manual
Hot-plug components
chapter "Important
section "Opening/closing the
(figure 34 on page
110) and can be
109