Connecting The Room Thermostat Or Zone Valves - Biasi Inovia 25C User Manual And Installation Instructions

Inovia series wall hung, fanflue, roomsealed, high efficiency gas boiler
Table of Contents

Advertisement

Allow the cables to exit the boiler by using
the relevant cable clamps Y (Fig. 6.17).
Fig. 6.17
6.10 Connecting the room thermo-
stat or zone valves
Use the clamps indicated in Fig. 6.15 to
connect the ambient thermostat.
Remove the electric jumper present be-
tween "1 and 3" when connecting any
type of ambient thermostat.
The electric cables of the ambient thermo-
stat are inserted between clamps "1 and 3"
as in Fig. 6.18 or Fig. 6.19 or Fig. 6.20.
Be careful not to connect pow-
ered cables on clamps "1 and
3".
INSTALLATION
Y
Potential clean contacts
of the Ambient
Thermostat
T
Fig. 6.18
Room thermostat
(230V rating)
T
Fig. 6.19
Room thermostat
T
with delay resistor
(230V rating)
Fig. 6.20
The thermostat must be insulation class II ( )
or must be correctly connected to earth.
1
N
L
3
2
1
N
L
3
2
1
- 57 -