activated.
11
12
13
14 15
Fig. 8.3
Fig. 8.4
• Scroll the various parameters using keys
17 or 18 until the letters P05 are displayed
on the LCD display, indicating that "pa-
rameter 05" (Fig. 8.5) has been activated.
Fig. 8.5
• Pressing the 11 key 5 times it is possible
to modify the value of parameter 5 (see
table).
Parameter
00
05
• By pressing key 14 (Fig. 8.3) confirmation
of the inserted value is obtained.
- 78 -
GAS CONVERSION
19
18
17
16
Gas type
G20
G31
• Press keys 17 or 18 (Fig. 8.3) to exit with-
out changing the value.
• Exiting the "programming mode" is au-
tomatic, after 15 minutes, or by cutting
power.
• Calibrate the gas valve according to the
instructions given in the Service manual,
section Gas valve - Adjustment.
• Reposition the controls panel and re-
mount the front panel of the body.
• Apply the label indicating the gas nature
and pressure value for which the appli-
ance is regulated. The self adhesive label
is contained in the transformation kit.