To install an IRC:

6.2
1.
Be sure the UPS system is turned off and all power sources are removed.
(See the operation section of this manual for shutdown instructions.)
2.
Install the IRC into an open X-Slot on the rear panel of the UPS Cabinet.
Remove X-Slot cover panel to gain access to the X-Slot.
3.
Install wiring from the IRC to the monitoring equipment using ½-in. conduit
through the cable exit opening in the IRC (see Figure 6---1).
4.
Connect wiring between the the IRC and the monitoring equipment using
terminations shown in Table 6---1. See Figure 6---1 for plug-in terminal block
locations.
IRC Terminal
Maximum contact rating: 250 VAC, 30 VDC @ 5A
Wire Range: 16---24 AWG
5.
To check the operation of the IRC, ensure that the UPS system is supplying the
load via the inverter or bypass. If the indicators on the customer's monitoring
equipment show the appropriate status, then it is operating correctly.
If the IRC is not operating correctly, check the wiring, the fuse on the IRC, and
the plug-in terminal blocks for proper seating. If all connections are secure but
the IRC still does not operate correctly, replace the fuse. If this does not
correct the problem, contact your local field service office for verification that
the IRC is working correctly.
6--2
Table 6---1. IRC Wire Terminations
J2---1
J2---2
J2---3
J2---4
J2---5
J2---6
J2---7
J2---8
J2---9
J2---10
J2---11
J2---12
Function
NC
COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
NO
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
Remarks
Normal Mode
Bypass Mode
Battery Mode
Alarm Mode
164201300 Rev. N 013004