16.
Bypass and output overcurrent protection and bypass and output disconnect switches are
to be provided by the user. Table W lists the maximum rating for bypass and output circuit
breakers satisfying the criteria for both.
Table W. Maximum Bypass and Output Circuit Breaker Ratings
17.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at the computed voltage.
A ---18
Powerware System
Powerware System
9330---20/10
9330---20/15
9330---20/20
9330---40/25
9330---40/30
9330---40/35
9330---40/40
Output Voltage Rating
208/220V
480V
35
15
60
25
70
30
90
40
110
45
125
60
150
60
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION:
L
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
600V
15
20
25
30
40
45
50
SHEET:
17 of 17
DATE:
041503
164201300 Rev. N 013004