Powerware 9330 Installation & Operation Manual page 198

10–20 kva/25–40 kva
Table of Contents

Advertisement

1.
The UPS equipment operating environment must meet the size and weight requirements
shown in Table AA, according to your UPS system configuration.
2.
In the UPS system, the UPS, Options, and Battery cabinets are palleted separately for
shipping.
3.
Do not tilt cabinets more than
4.
Dimensions are in millimeters (inches).
Table AA. Equipment Weight
Table AA Equipment Weight
UPS Cabinet with Filter and Batteries
Powerware 9330 (10 kVA ---20 kVA)
UPS Cabinet with Filter and Batteries
Powerware 9330 (25 kVA ---40 kVA)
Options Cabinet with PDM and no transformer
Powerware 9330 (10 kVA ---20 kVA)
Options Cabinet with PDM and 1 transformer
Powerware 9330 (10 kVA ---20 kVA)
Options Cabinet with PDM and 2 transformers
Powerware 9330 (10 kVA ---20 kVA)
Options Cabinet with PDM and no transformer
Powerware 9330 (25 kVA ---40 kVA)
Options Cabinet with PDM and 1 transformer
Powerware 9330 (25 kVA ---40 kVA)
Options Cabinet with PDM and 2 transformers
Powerware 9330 (25 kVA ---40 kVA)
Battery Cabinet
NOTES:
Powerware 9330 (10 kVA ---20 kVA)
Powerware 9330 (25 kVA ---40 kVA)
5.
The clearances required around the UPS System are shown in Table AB.
Table AB. System Clearances
From Front of Cabinet
From Back of Cabinet
From Sides of Cabinet
A ---24
10˚ during handling.
Component
Component
1. For UPS Cabinet without Filter, subtract 25 Kg (55 lb).
2. For UPS Cabinet without Batteries, subtract 227 Kg (499 lb)
3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)
4. For Options Cabinet with Distribution Housing, add 11 Kg (25 lb)
1. For UPS Cabinet without Filter, subtract 41 Kg (90 lb).
2. For UPS Cabinet without Batteries, subtract 453 Kg (998 lb)
3. For Options Cabinet without PDM, subtract 11 Kg (25 lb)
Shipping
461 (1017)
873 (1925) 838 (1847)
118 (260)
240 (530)
358 (790)
154 (340)
471 (1040)
782 (1725) 748 (1650)
361 (795)
36 inches working space
12 inches air circulation clearance
Allow space for Options and Battery Cabinets
DESCRIPTION:
PHYSICAL FEATURES AND REQUIREMENTS
DRAWING NO:
164201300---3
REVISION:
N
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
Weight
Kg (lb)
Installed
Point Loading
435 (958)
6 at 73 (160)
9 at 93 (205)
90 (200)
4 at 23 (50)
213 (470)
4 at 53 (118)
331 (730)
4 at 83 (183)
120 (265)
6 at 20 (44)
437 (965)
6 at 73 (161)
6 at 125 (275)
333 (735)
6 at 56 (123)
SHEET:
DATE:
013004
164201300 Rev. N 013004
1 of 2

Advertisement

Table of Contents
loading

Table of Contents