Powerware 9330 Installation & Operation Manual page 205

10–20 kva/25–40 kva
Table of Contents

Advertisement

AC INPUT TO
UPS RECTIFIER
(DUAL FEED)
3 WIRE A--- B--- C
ROTATION
SEE NOTE 1
REMOTE
BATTERY
INPUT
C
E4. E5
INTERNAL
BATTERY
EXTERNAL
BATTERY
BATTERY
CABINET
(Optional)
UPS SYSTEM WITH 208V/220V INPUT AND 208V/220V OUTPUT,
NOTE 1: Remove jumper for dual feed.
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 Rev. N 013004
AC INPUT TO
UPS RECTIFIER
(SINGLE FEED)
AC INPUT
TO BYPASS
(SINGLE OR DUAL FEED)
4 WIRE A--- B--- C
ROTATION
A
B
E1, E2, E3
E6, E7, E8, E12
CB1
OPTIONAL
INPUT FILTER
INPUT
CONTACTOR
(K1)
RECTIFIER
(K2)
CB2
BATTERY
SWITCHES
BATTERY
BREAKER
DC --- DC
CONVERTER
INVERTER
BATTERY
BREAKER
SINGLE OR DUAL FEED
POWERWARE 9330 (10 kVA---20 kVA)
POWERWARE 9330 (25 kVA---40 kVA)
(See Tables X, Y, and Z)
RS--- 232
CAN INTERFACE
REMOTE EPO
COMMUNICATIONS
SERVER
MAINTENANCE
BYPASS
SWITCH
FUSE
BACKFEED
CONTACTOR
(K5)
STATIC
SWITCH
FUSE
OUTPUT FILTER
OUTPUT
CONTACTOR
(K3)
UPS CABINET
DESCRIPTION:
ONELINE DRAWINGS OF UPS SYSTEM
DRAWING NO:
164201300---6
REVISION:
L
BUILDING ALARMS
GENERAL
PURPOSE RELAYS
X-SLOT
INTERFACE
D
AC OUTPUT
TO
E9, E10,
CRITICAL LOAD
E11, E12
SHEET:
DATE:
041503
1 of 1
A ---31