6.
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range:
Recommended Operating Range: 20---25˚C (68---77˚F)
Maximum Relative Humidity:
The UPS ventilation requirements are shown in Table AC.
Table AC. Air Conditioning or Ventilation Requirements
Ratings
10 KVA
15 KVA
20 KVA
25 KVA
30 KVA
35 KVA
40 KVA
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 Rev. N 013004
During Full Load Operation
Powerware 9330 (10 kVA-- 40 kVA)
Input/Output Voltage
208/208, 208/220, 220/208, 220/220
480/208, 600/208
480/480
208/208, 208/220, 220/208, 220/220
480/208, 600/208
480/480
208/208, 208/220, 220/208, 220/220
480/208, 600/208
480/480
208/208, 208/220, 220/208, 220/220
480/208, 600/208
480/480
208/208, 208/220, 220/208, 220/220
480/208, 600/208
480/480
208/208, 208/220, 220/208, 220/220
480/208, 600/208
480/480
208/208, 208/220, 220/208, 220/220
480/208, 600/208
480/480
0---40˚C (32---104˚F)
95%, noncondensing
Heat Rejection*
BTU/hr ¢ 1000/hr (Kg---cal/hr)
2.1 (0.53)
2.7 (0.7)
3.6 (0.9)
3.1 (0.8)
4.0 (1.1)
5.3 (1.3)
4.2 (1.1)
5.4 (1.4)
7.1 (1.8)
5.2 (1.3)
6.7 (1.7)
8.9 (2.2)
6.3 (1.6)
8.0 (2.0)
10.7 (2.7)
7.3 (1.8)
9.3 (2.4)
12.5 (3.1)
8.3 (2.1)
10.7 (2.7)
14.3 (3.6)
DESCRIPTION:
PHYSICAL FEATURES AND REQUIREMENTS
DRAWING NO:
164201300---3
REVISION:
L
SHEET:
2 of 2
DATE:
041503