8.
Remove three bolts, (2) in Figure 2---1, securing front shipping bracket to the
cabinet.
9.
If installing cabinet permanently, retain shipping brackets and hardware;
otherwise, discard or recycle the pallet and brackets in a responsible manner.
10.
Roll cabinet to final installation location.
11.
If permanently mounting the system, proceed to step 16; otherwise, proceed to
step 12.
12.
Secure the UPS cabinet in position by lowering the leveling feet, until cabinet is
not resting on the casters and the cabinet is level.
13.
If installing Battery and Options cabinets, proceed to step 14; otherwise,
proceed to paragraph 2.2.4.
14.
If installing an Options cabinet with Distribution Housing, proceed to paragraph
2.2.2; otherwise, proceed to step 15.
15.
Install Battery cabinets and Options cabinet without Distribution Housing, by
repeating steps 1 through 10 for remaining cabinets and then proceed to
paragraph 2.3 for Battery cabinet installation and paragraph 2.4 for Options
cabinet installation.
16.
Using retained hardware, reinstall shipping brackets previously removed to
front and rear of UPS cabinet with the angle facing outward (see Figures 2---1
and 2---2).
17.
If installing Battery and Options cabinets, proceed to step 18; otherwise,
secure cabinet to floor with contractor supplied hardware and proceed to
paragraph 2.2.4.
18.
If installing an Options cabinet with Distribution Housing, proceed to paragraph
2.2.2; otherwise, proceed to step 19.
19.
Install Battery cabinets and Options cabinet without Distribution Housing, by
repeating steps 1 through 10 for remaining cabinets and then proceed to
paragraph 2.3 for Battery cabinet installation and paragraph 2.4 for Options
cabinet installation.
2.2.2
Unloading the Powerware 9330 (10 kVA---20 kVA) Options

Cabinet with Optional Distribution Housing from the Pallet

The Options cabinet is bolted to a wooden pallet supported by wood skids. To
remove the pallet, perform the following procedure:
WARNING:
The options cabinet is heavy. Refer to Drawing 164201300- -3 in Appendix A
for weight of cabinets. If unloading instructions are not closely followed, the
cabinet may cause serious injury.
CAUTION:
Do not tilt cabinets more than 10 degrees from vertical.
1.
Use a forklift or other material handling equipment to move the cabinet to the
installation area. Insert the forklift jacks between the skids on the bottom of
the unit.
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation