Powerware 9330 Installation & Operation Manual page 182

10–20 kva/25–40 kva
Table of Contents

Advertisement

Basic unit ratings at
0.7 lagging PF load
AC Input to UPS Rectifier
AC Input to UPS Rectifier
AC
AC
Transformer
Transformer
INPUT
(0.95min.PF)
(
3  1
3 , 1 gnd
AC Input to UPS Bypass
AC Input to UPS Bypass
AC
AC
Transformer
Transformer
INPUT
Full Load Current
3 , 1 Neutral, 1 gnd
3  1 N
NOTE:
Callout letter
map to drawing #164201300---6
A ---8
Table K. Ratings & External Wiring Requirements for
Powerware 9330 (25 kVA---40 kVA)
Options Cabinet INPUT and BYPASS Transformers
g
Series/
Model
40/25
40/25
40/25
40/30
40/30
40/30
)
40/35
d
40/35
40/35
40/40
A
40/40
40/40
40/25
40/25
40/25
40/30
40/30
40/30
40/35
l 1
d
40/35
40/35
40/40
B
40/40
40/40
and
,
,
,
Ratings 50/60 Hz
Voltage
Input
Output
kVA/KW
25/17.5
208
25/17.5
480
25/17.5
600
30/21
208
30/21
480
30/21
600
35/24.5
208
35/24.5
480
35/24.5
600
40/28
208
40/28
480
40/28
600
25/17.5
208
25/17.5
480
25/17.5
600
30/21
208
30/21
480
30/21
600
35/24.5
208
35/24.5
480
35/24.5
600
40/28
208
40/28
480
40/28
600
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION:
L
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
Conductor
Input
Input
Minimum
Current
Size
(Amps)
208
69.4
4
208
30
8
208
24
10
208
83
2
208
36
8
208
28.8
10
208
97
1
208
42
6
208
33.6
8
208
111
1/0
208
48
6
208
38.5
8
208
69.4
4
208
30
8
208
24
10
208
83
2
208
36
8
208
28.8
10
208
97
1
208
42
6
208
33.6
8
208
111
1/0
208
48
6
208
33.5
8
SHEET:
DATE:
041503
164201300 Rev. N 013004
7 of 17