Installing a Remote EPO Control

4.1 Installation Procedures

4.2 To Install a Remote EPO:

NOTE: Before installing a Remote EPO, be sure you have prepared the UPS according
to the instructions in Chapter 2.
To Install a Remote EPO control:
1. Securely mount the remote EPO switch. Recommended locations include near
operator's consoles or near exit doors. Refer to Remote EPO switch manufacturers
installation instructions for enclosure dimensions and wiring knockouts.
2. Install wiring from the remote EPO switch using appropriate sized conduit through
the Customer Interface conduit landing plate on the bottom rear of the UPS cabinet.
Refer to Figure A-10 for conduit landing area,
3. Connect the Remote EPO wiring as shown in Tables 4–1 and 4–2.
Powerware 9335 (80 kVA and 120 kVA) Installation and Operation
164201396 REV A 071103
EMERGENCY OFF
Figure 4–1. Typical Remote EPO Control