13.7.2 Event History Log

This key sequence prints the entire Event History Log of the UPS at the time the
data is requested. The printout begins with the oldest alarm entry in the queue and
ends with the most recent. Any alarms that occur while the Event History Log is
printing are included in chronological order.
The Event History Log lists up to 500 system events in chronological order with the
most recent event listed last. Figure 13---19 shows a sample Event History Log
printout.
In this mode, system events are continually logged through the serial port to the
device connected to the port.
The printed log entries contain a time and date stamp and the alarm text message.
Terminal mode uses this format for printing alarm entries:
MM DD YYYY
An alarm message is prefixed by the word "CLEAR" whenever an alarm is entered
into the Event History Log with a cleared status.
If a port is operating in Terminal mode and is connected to a computer, you can
use key combinations at any time to print selected information:
Esc+H
To use a key combination, hold down the Esc key and press the letter key.
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 Rev. N 013004
HH:MM:SS.hh
Symbol
Description
MM
Month (2 digits)
YYYY
Year (4 digits)
DD
Day (2 digits)
HH
Hour (2 digits)
MM
Minute (2 digits)
SS
Second (2 digits)
hh
Hundredths of Second (2 digits)
KYWD
Keyword (ALARM, NOTICE, COMMAND, or STATUS)
System Diagnostic Information
::::
<CR>
Carriage Return Character (ASCII 13)
<LF>
Line Feed (ASCII 10)
Prints the entire log with a firmware version header
KYWD MESSAGE
::::
<CR> <LF>