Weil-McLain GV90+ Installation And Start-Up Manual page 82

Series 2 gas-fired water boilers
Hide thumbs Also See for GV90+:
Table of Contents

Advertisement

GV90+
Series 2
oAs·FIRED WATER BOILER -
Boiler Manual
Troubleshooting
(cootinuedJ
Figure 96 Common
causes
and
possible
corrections,
part
2
Symptom
Common Causes
Possible Corrections
Popping
or percolating
Mineral deposits
in sections due
Call
qualified
service
technician to
de-
noise heard
in boiler
to
constant
use
of
makeup
water
lirne
boiler, if
necessary.
In
some cases,
deposits
will
be too
heavy to remove
with
de-liming
procedures.
Have
qualified
service technician
repair
leaks
to eliminate
need
for constant
makeup
water.
Incorrect
pH
of
boiler
water
Call
qualified
service
technician to check
pH
level
and
correct. pH
should
be
maintained
between 7.0
lo
8.5.
Insufficient water
flow through
Ch.eck all valves
lo
and
from boiler.
Return
boiler
to
proper
seHing.
Confirm
circulator
size.
Metal flakes found
in
vent
Contaminated
combustion air
R&move
any contaminating
products,
see
outlet or
recuperator -
supply
- See manual
page 30.
manual
page
30.
flueway
corrosion
Provide outside
air
for combustion. Have
qualified
service technician
pipe-up kit
Condensation of
combustion
Have qualified service
technician check
gases
in
boiler
sections
operation of mixing system.
Repair/replace
if
necessary.
Some
radiators.
or
Air in system
Bleed
air
from system
through air
veniS in
baseboard units
do
not
radiators or baseboard
units.
heat
or are
nois
y
Low
system
pressure
Fill
to
correct
pressure.
Ch.eck
for
leaks in
boiler
or
piping. Have
qualified
service
technician
repair at
once.
High
limit
set
too
low
Adjust
high
limit
to
higher
seHing.
82
Pan
number
550-142-783/1012