Weil-McLain GV90+ Installation And Start-Up Manual page 75

Series 2 gas-fired water boilers
Hide thumbs Also See for GV90+:
Table of Contents

Advertisement

GV90+
Series
2
GAs·FIRED WATER BOILER -
Boiler Manual
Service & maintenance
(ccntinuedJ
Figure 83
Recuperator
flueway dra in holes
G4006
thoroughly
flu.
s bed with fresh
water,
allow
r.he water to
drain
out through the
recuptrnt:Or
condensate opening..
6.
Dump
any remaining water f'rom the
recuptrnt:Or.
7.
Look through the flue adapter aud locate the flueway drain
holes as
shown
in Figure 83.
8.
Use
a brush
or
other
mean.s
to remove blod:age f'rom these
holes.
9.
Rinse rhe
r«uperator
thoroughly.
IAWARIINO
I
If
the
recuperator shows
signs
of
significant
cor-
rosion
o
r
deterioration, contacr Weii-Mctain
for
TtCOrnmendarions
on
im·estigating
the
cause and
replacing
the recupe-rator if necessary.
Re-install
the
recuperator
I.
lnspecr the
rtcuperaror
gaskets to make sure all art in good
condition. Replace if there
is
an)'
sign of
damage.
2.
Atrach
the
recupe-rator at the
boiler
connection.
3.
Secure
with
the
four
nurs.
4.
Re-connect
rh~
water connecrions
ro
the
upper
and lower
recuperator
flanges.
5.
Re-Insert
the l.n-llne drain fitting Into the recuperator
>
'ellt
adaprer.
Tighten the
clamp
ro
secure
in
p
l.ac~.
6.
R~-co nnect
the
plug-in
connector
on
the thermal
fuse
(Fig-
ure 102,
page
97,
irem 27).
Part
number 550-1+2-783/1012
Re-install th
e
condensat
e t
rap
tiw
ARteG)
Make sure
the
condensate
trap is
re-installed
securely.
'
F ailure to comply
with
the above could result in
~·t"Te
persona]
injury, death or
substantial property
damage.
Re-connect t
he vent
pipe
I.
If the
vent
pipe
was
lifted
out. re-insert
the
venr
pipe into.
2. If the
vent
pipe
was
cut, install
a
coupling
in
the vtnr line
to
aJJow re-oonnection.
3.
If a
section
was removed
(stainless
·•~nt
pipe), replace the
S«t.ion.
4. Re-co
nnect the
vent
pipe to the ln-liue drain fitting and
tighre:n
rJt..e
damp.
When rtplacing the vtnr
pipe,
follow
all instruc-
t ions
in
this
manual
to ensure
rhe
•tent is
prope:rl)•
.compl
~td.
Failure ro
properly
the
v~nt
pipe
could
Tt'Sult
in
kVere
personal
injury,
death
or
substantial
propcty damag<.
75