Caution
Always wipe any drip of gasoline or oil.
Add fuel to the fuel tank
① ① ① ①
② ② ② ②
Turn the starter switch to <RUN> position. It will take approximately 30 seconds to
vacuum the air out.
<Caution>
Ensure that all the air is completely extracted from fuel line, by setting the throttle lever
to IDLING and start the engine. In the case air is in the fuel line, the engine speeds is
unstable, and proceed with the vacuuming steps again.
9.4 Stopping the Generator
① ① ① ①
Turn the switch and the circuit breaker for the load equipment to OFF
Turn the circuit breaker for single-phase and 3-phase on the control panel to OFF
② ② ② ②
position
③ ③ ③ ③
Set the throttle lever to IDLING
Keep the engine idle (cooling down) for at least 3 minutes
④ ④ ④ ④
⑤ ⑤ ⑤ ⑤
Turn the starter switch to STOP position
9.5 Protection Features
This generator is equipped with automatic shutdown feature and display of the location of alarm,
in event of any alarm situation. In event of the automatic shutdown or alarm lamp flashing, turn
off the engine and investigate the alarm.
Protection Feature List
No.
Symptoms
High Coolant
1
temperature
Oil pressure
2
drop
Insufficient
battery
3
charge
Current
leaks to the
4
earth
Overload
5
○ ○ ○ ○
indicate the automatic feature
:Fire
Circuit
Automatic
Breaker
OFF
--
--
--
○ ○ ○ ○
○ ○ ○ ○
- 36 -
Action
Alarm
Engine
Lamp
Shutoff
Flash
○ ○ ○ ○
○ ○ ○ ○
○ ○ ○ ○
○ ○ ○ ○
--
○ ○ ○ ○
--
○ ○ ○ ○
--
--
Cause
Engine coolant temperature
is too high
(default at 105 degrees Celsius)
Engine oil pressure dropped
(default at 0.98 x 100kPa)
2
(1.0kg/cm
)
When the battery can no longer
hold charge
When current leaks to the earth
When the circuit overloads