9.2 200/400 Voltage Changeover - Dual Voltage System
The generator is incorporated with dual voltage system.
So, you can easily change 400/440V to 200/220V or adversely.
You can get 200V or 400V by changing the combination of output terminals with bus plates
Danger
:Electrical Shock
Be sure to set the circuit breaker OFF and stop operation before setting.
Caution
: Damages to the property
Be sure to set the bus plates at the right positions and screw them securely.
Always ensure that the bus plate combination is correct (200V or 400V), connections
of cables to the output terminals are correct and the voltage of loads is correct to use.
Turn off the both 3-Phase and 1-Phase breakers to OFF.
① ① ① ①
Open the box cover next to the control box and change the 6 bus plates connected to the
② ② ② ②
output terminals to the required voltage combination.
3-PHASE 200/220V
BUS PLATES
(The left side toward the control panel)
WARNING LABEL
(PART No.19402-00291)
3-PHASE
OUTPUT
OUT TERMINAL
TERMINAL
COVER
- 34 -
BOX COVER
(Terminals and Bus plates are
inside this cover)