Programming Function Blocks and Features

Table 4-72 Prompts For Storage Setup Of Trends, Alarms, Events, Diagnostics

Prompt
POINT #1 -
Analog or discrete parameter
POINT #12
STORAGE MODE
CONTIN, BATCH, or NONE
COPY DISPLAY
SETUP
LOW RATE
Seconds: .5, 1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 20, 30, 40, 50
Minutes: 1, 2, 3, 4, 5, 10, 15, 20,
30, 40, 50
Hours: 1
HIGH RATE
Seconds: .5, 1, 2, 3, 4, 5, 6, 7, 8,
9, 10, 20, 30, 40, 50
Minutes: 1, 2, 3, 4, 5, 10, 15, 20,
30, 40, 50
Hours: 1
ROLLOVER
ON, OFF
SET DISPLAY
OFF or number
LIMITS
HIGH RATE
SELECTOR
SELECTORS
CHANGE WITH KEY
EXTERNAL
OFF, discrete parameter, 0, 1
ENABLE
SELECT
FILE
PROD
FILENAME
UNIT
CONFIG
CALIB
FURNCE
BATCH
LINE
ZONE
168
Range/Selections
CYCLE
DRYER
RECORD
TANK
LOOP
REACTR
KILN
VESSEL
WCHEM
PRESS
DEMIN
CONTRL
FERMTR
LEHR
STRLZR
OVEN
Video Recorder – User Manual
Definition
Select the data points for the trend.
Continuous storage becomes active immediately upon
initialization. Batch storage is controlled by a discrete
parameter (see BATCH CONTROL) or by start/stop batch
menu item. Batch data may be started and stopped several
times in a single file until the file is full. Batch start
increments a batch number that is stored along with the
data. The batch number may be used for data retrieval and
analysis using SDA data analysis software.
Select this to copy the following Trend 1,2, 3 or 4 Display
data to Trend 1,2, 3 or 4 Storage data: Point #1–#12, set
display limits, timebase (high rate) selector. Once setup is
copied, it can be altered.
Enter data collection rate. This is how often the data points
are sampled.
Enter data collection rate. This is how often the data points
are sampled.
Select ON to continue gathering and storing data after the
file becomes full. The new data will replace the oldest data
on the disk as it is collected. No warning will be given.
Select OFF to stop storage of this data type when the disk
space for it becomes full. A "DISK FULL" message will then
appear. Data is buffered until a new disk is inserted and
initialized.
Enter upper and lower limit values for the trend display for
each point. If OFF then the trend will use the programmed
limits for each point.
This discrete triggers the high storage rate when ON(1) and
the low storage rate when OFF.
This option enables/disables storage rate changes from the
Trend display Point/Trend menu. If YES, storage Trend's
high rate will be used when display Trend's alternate
timebase is selected from the Online Point/Trend menu;
Storage Trend's low rate will be used when display Trend's
normal timebase is selected. See Table 6-2, Point/Detail
Menu Prompts, Timebase.
When ON(1), this discrete parameter will allow storage of
the data type; when off storage for the data type will stop.
This enable is independent of the storage mode; it does not
control batch start/stop.
Select a file name to identify the type of data to be stored.