Diagnostic and error messages
Error
Trend Has Too Many
Points For Rate Selected
Type Does Not Exist
Type Incompatible With
Hardware
Type Requires Hardware
Undefined Function Block
Request
Value Written to
Indirected Point
X Axis Must Increase
X Axis Not Increased
Enough
Y Axis Not Increased
Enough
258
Table 9-4 Error Messages (continued)
Description
Data Storage cannot store more than 3 points at 1/4
second scan rate.
A function block type was loaded that does not exist.
For example, you loaded a Profile but the unit does
not have the Profile option.
Analog output type is different from hardware setting.
th
Attempted to assign 6
relay as a DAT function.
Hardware is missing for the programmed analog
output or discrete output relay.
Internal Error.
An input has been connected and user has tried to
write a value to that input. For example, if a control
loop setpoint is connected to AI1 OV, you will receive
this message if you try to change the loop setpoint
online.
Appears if AI is custom type or CV is Function
Generator and if Xn > Xn+1.
Appears if AI is custom type or CV is Function
Generator and if X does not increase by at least
0.00001.
Appears if AI is custom type or CV is Function
Generator and if Y does not change by at least
0.00001.
Video Recorder – User Manual
User Action
Change number of points to be
compatible with scan rate.
Re-program or re-load correctly.
Change programming to be
compatible with the hardware or
vice versa, then reload
configuration or reconfigure the
block.
Either ignore the message
knowing that those particular
points did not get loaded or verify
configuration and make sure that
the points that are in the
configuration match the hardware
components.
No user action.
Avoid changing connected values.
Re-program Xn < Xn+1.
Re-program X.
Re-program Y.