Diagnostic and error messages
Error
Incorrect Input
coordinates
Incorrect Number of
Parameters for function
Incorrect Output
Coordinates
Invalid Algorithm Code
Invalid Block Number
Invalid Block Type
Invalid Channel in Point
spec
Invalid Equation
Invalid Function Block
Request
Invalid Index code
Invalid Input Connection
Invalid Machine Update
Rate
Invalid Parameter Code
Invalid Parameter for
Data Type
Invalid Tag
Invalid Tag Request
Invalid Type in Point
Spec
Lag or Delay Less than
Zero
256
Table 9-4 Error Messages (continued)
Description
The Advanced Splitter CV was programmed with
input limits for Output#2 (A2) only, or for Output#1 &
#3 (A1 & A3) only, or for Output#3 (A3) only.
The function was not programmed with the minimum
number of parameters. for example, the Math CV
requires at least 2 inputs to function properly.
The Advanced Splitter CV was programmed with
output limits for Output#2 (A2) only, or for Output#1 &
#3 (A1 & A3) only, or for Output#3 (A3) only.
Bad algorithm code has been given, bad algorithm
choice. Probably caused by someone incorrectly
editing the configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Invalid channel has been found.
Free form math equation is invalid.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Function block is programmed with wrong input type.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Bad machine scan rate.
Bad parameter code has been found. Generally
caused by transferring configurations between
instruments with different software versions.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
Probably caused by someone incorrectly editing the
configuration file or by a corrupt .LNC file.
A class of block was detected that is invalid for the
product.
AI lag or delay is less than zero.
Video Recorder – User Manual
User Action
Re-program input limits for
Output#1 only, Outputs #1 & #2,
or Outputs #1, #2, & #3.
Program function with at least the
minimum number of parameters.
Re-program output limits for
Output#1 only, Outputs #1 & #2,
or Outputs #1, #2, & #3.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Check equation.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Re-enter machine scan rate.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Verify programming of affected
function block.
Change lag or delay to greater
than or equal to zero.