Table 4-49 CEMS Rolling Average Prompts

Prompt
RANGE LOW
RANGE HIGH
INPUT
RESET
TIME UNITS
AVERAGE PERIOD
FRAME PERIOD
CALIBRATE HOLD
142
Range/Selections
OFF or number
Enter the output's display limits. Output is not clamped or flashed
when it exceeds these limits.
OFF, analog
Input to be averaged.
parameter, number
OFF, discrete
When discrete is ON(1), average is reset to zero; when ON(1)-to-
parameter, 0, 1
OFF(0), average restarts.
Seconds, minutes,
Time units of the averaging period.
hours, or days.
OFF or number
Number of time units per average period.
OFF or number
Number of time units per Frame Period. Must divide evenly into
Average Period.
OFF, discrete
When ON(1), no samples are taken and the output is held.
parameter, 0, 1
If calibrate hold is set ON, the function block stops acquiring
samples; however, the averaging will continue to update for the
remainder of the average period, after which, the output value will
hold.
If calibrate hold is set ON longer than the average period, the
display will alternate between the last output value and
*****(indicating the current value is no longer valid).
If calibrate hold is set OFF and the CEM Rolling Average is not
reset, the CEM Rolling Average will continue to update every frame
period from the last value. If the CEM Rolling Average is reset, the
average value is set to zero and the displayed value will not update
until the Average period has transpired. The average value will
update every frame period.
Video Recorder – User Manual