Install the new burner (see fig. 79).
WARNING!
Fit the burner so that the scale mark is located on
the left-hand side (see fig. 79).
Re-assemble all other parts in reverse order of disassembly.
Open the gas shut-off valve (see fig. 80, pos. 2).
Switch on the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "1" (On).
Also check all joints and gaskets affected by the replacement
activities while carrying out the tightness test in operating
conditions.
Set the gas/air ratio again. See paragraph 8.1.26.
8.1.31 Sight glass; replacing
Switch off the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "0" (Off).
Remove the casing.
Loosen both screws of the sight glass (see fig. 81, pos. 1).
Remove the sight glass mounting plate.
Disassemble the sight glass inclusive of both gaskets.
Assemble the new sight glass and all further parts in reverse
order of disassembly; remember to fit new gaskets.
Fit the casing.
Switch on the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "1" (On).
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
fig. 79
Installing the burner
fig. 80
Gas shut-off valve closed (1), gas shut-off valve
open (2)
fig. 81
Loosening the screws of the sight glass
Actions
8
1
115