Yes - Buderus Logamax plus GB142-24 Servicing Instructions

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB142-24:
Table of Contents

Advertisement

7
Diagnosis
Repl. BB
page 34
21
Check that the tank filling pump
is running.
Is the tank filling
pump running?
Check that during hot water mode there is a
120V AC voltage on the tank filling pump.
Is the tank filling pump
being activated?
Check the connection board to make sure that
there is 120V AC on both contacts L and N of
connection PS (gray) during hot water mode.
Does
the connection board
have on both contacts L and N of
connection PS 120V AC during hot
water operation?
Check the fuse on the connection board.
Value: 5A. See page 84.
Is the fuse
on the connection board
okay?
Check the cable loom of the device.
Is the cable loom okay?
Replace the circuit board.
Is the tank filling pump
running?
44
page 83
36
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!

Yes

No
Yes
No
Yes
No
No
Yes
No
Yes
Yes
No
45
page 37
46
page 37
Replace the supply
cord of the tank-filling
pump.
Replace the fuse on
the connection board.
See page 84.