8.1.8
Replacing the supply/return/safety sensors
Switch off the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "0" (Off).
Remove the casing.
Close the maintenance shut-off valves.
Drain the Logamax plus GB142.
Disconnect the plug and socket connection.
Unscrew the sensor concerned and replace it by a new one.
Supply sensor see fig. 16, pos. 1.
Return sensor see fig. 16, pos. 2.
Safety sensor see fig. 17, pos. 1.
Restore the plug and socket connection.
Open the maintenance shut-off valves.
Purge air from the boiler.
NOTICE
Fill and purge the Logamax plus GB142 as
required. See installation and maintenance instruc-
tions Logamax plus GB142-24/30/45/60.
Fit the casing.
Switch on the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "1" (On).
8.1.9
Checking the hot-water temperature sensor
Switch off the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "0" (Off).
Remove the casing.
Disconnect the plug and socket connection of the cable for the
hot-water temperature sensor.
Pull out the sensor and replace it by a new one.
Restore the plug and socket connection.
Fit the casing.
Switch on the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "1" (On).
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
1
2
fig. 16
Replacing the supply/return sensors
1
fig. 17
Replacing the safety sensor
Actions