"H" Group: Motor Constants Functions

"H" Group: Motor Constants Functions
Introduction
Func.
Name
Code
H001 Auto-tuning Setting
H002 Motor data selection,
1st motor
H202 Motor data selection,
2nd motor
H003 Motor capacity, 1st
motor
The "H" Group parameters configure the
inverter for the motor characteristics. You
must manually set H003 and H004 values
to match the motor. Most of the remaining
parameters are related to vector control, and
are in use only when function A044 is set
for one of the vector control modes as
shown in the diagram. The procedure in
"Auto-tuning of Motor Constants" on
page 4–67
automatically sets all the param-
eters related to vector control. If you
configure the inverter to use vector control,
we highly recommend letting the auto-
tuning procedure derive the values for you.
If you want to reset the parameters to the
factory default settings, use the procedure
in
"Restoring Factory Default Settings" on
page
6–9.
NOTE: The auto-tuning procedure and related warning messages are in
Constants" on page
4–67. Please read these before trying to auto-tune the motor parameters.
"H" Function
Description
Three states for auto-tuning
function, option codes:
00 Auto-tuning OFF
01 Auto-tune (measure
motor resistance and
inductance, without
rotating)
02 Auto-tune (rotate motor)
Select one of three motor
parameter sets, 3 options:
00 Standard motor data
01 Auto-tuning data
02 Adaptive tuning data
Select one of three motor
parameter sets, 3 options:
00 Standard motor data
01 Auto-tuning data
02 Adaptive tuning data
Select 0.2 to 75.0kW for
models up to –550xxx,
0.2 to 160.0kW for models
–750xxx to –1500xxx
Inverter Torque Control Algorithms
V/f control,
constant torque
V/f control,
variable torque
V/f control, free-
setting curve
Sensorless vector
(SLV) control
Sensorless vector,
0Hz domain
Vector control with
sensor
Defaults
Run
Mode
Edit
–FE
–FU
–FR
Lo Hi
(EU)
(US)
(JP)
✘ ✘
00
00
00
✘ ✘
00
00
00
✘ ✘
00
00
00
✘ ✘
Factory set
A044
00
01
02
Output
03
04
05
"Auto-tuning of Motor
SRW Display
Units
>H001 AUX
AUTO
NOR
>H002 AUX
DATA
NOR
>H202 2AUX
DATA
NOR
kW
>H003 AUX
K
003.70kW