4–34
Using Intelligent Input Terminals
Force Operation
from Digital
Operator
This function permits a digital operator interface to override the Run command source setting
(A002) when it is configured for a source other than the operator interface. When the [OPE]
terminal is ON and the operator interface gives a Run command, the inverter uses the standard
output frequency settings to operate the motor.
Opt.
Symbol
Function Name
Code
31
OPE
Force Operation
from Digital
Operator
C001, C002, C003, C004,
Valid for inputs:
C005, C006, C007, C008
A001
Required
A002 (set not equal to 02)
settings:
Notes:
• When changing the [OPE] state during Run
Mode (inverter is driving the motor), the
inverter will stop the motor before the new
[OPE] state takes effect.
• If the [OPE] input turns ON and the digital
operator gives a Run command while the
inverter is already running, the inverter stops
the motor. Then the digital operator can
control the motor.
Input
Description
State
ON
Forces the operator interface Run
command to over-ride commands from
input terminals (such as [FW], [RV]).
OFF
Run command operates normally, as
configured by A002
Example: (Requires input configuration—
see page 3–47. Jumper position shown is
for –xFU/-xFR models; for –xFE models,
see page 4–12.)
TH
FW
CM1
8
P24
PLC
CM1
7
See I/O specs on page 4–9.
OPE
5
3
1
6
4
2