xiv
Fuse and Circuit
Breaker Sizes
Motor
Input
Output
Voltage
HP
kW
1/2
0.4
1
2
1.5
3
2.2
5
3.7
7.5
5.5
SJ300-055LFU
10
7.5
SJ300-075LFU
200V
15
11
SJ300-110LFU
20
15
SJ300-150LFU
25
18.5 SJ300-185LFU
30
22
SJ300-220LFU
40
30
SJ300-300LFU
50
37
SJ300-370LFU
60
45
SJ300-450LFU
75
55
SJ300-550LFU
Wire Connectors
Motor Overload
Protection
The inverter's input power wiring must include UL Listed, dual-element, 600V fuses, or UL
Listed, inverse-time, 600V circuit breakers.
Ampere Rating
200V
for Fuse or
Inverter Model
Breaker
10
10
10
15
20
30
40
60
80
100
125
150
175
225
250
WARNING: Field wiring connections must
be made by a UL Listed and CSA Certified
ring lug terminal connector sized for the
wire gauge being used. The connector must
be fixed using the crimping tool specified by
the connector manufacturer.
Hitachi SJ300 inverters provide solid state motor overload protection, which depends on the
proper setting of the following parameters:
• B012 "electronic overload protection"
• B212 "electronic overload protection, 2nd motor"
• B312 "electronic overload protection, 3rd motor"
Set the rated current [Amperes] of the motor(s) with the above parameters. The setting range is
0.2 * rated current to 1.2 * rated current.
WARNING: When two or more motors are connected to the inverter, they cannot be protected
by the electronic overload protection. Install an external thermal relay on each motor.
Motor
Input
Output
Voltage
Inverter Model
HP
kW
1
2
1.5
3
2.2
5
4.0
7.5
5.5
10
7.5
SJ300-075HFU/E
15
11
SJ300-110HFU/E
20
15
SJ300-150HFU/E
25
18.5 SJ300-185HFU/E
400V
30
22
SJ300-220HFU/E
40
30
SJ300-300HFU/E
50
37
SJ300-370HFU/E
60
45
SJ300-450HFU/E
75
55
SJ300-550HFU/E
100
75
SJ300-750HFU/E
125
90
SJ300-900HFU/E
150
110
SJ300-110HFU/E
175
132
SJ300-1320HFE
200
150
SJ300-1500HFU
Terminal (ring lug)
Ampere Rating
400V
for Fuse or
Breaker
10
10
10
15
15
20
30
40
50
60
70
90
125
125
175
200
250
300
300
Cable support
Cable

Advertisement

Table of Contents
loading

Table of Contents