Wiring Terminals
Host computer
RS-232C: 25-pin
SD (TXD)
RD (RXD)
RS (RTS)
CS (CTS)
DR (DSR)
SG
ER (DTR)
FG
External Power Supply for
ES1B
RS-232C (E5AN/EN Only)
• When communications are to be used with the E5AN/EN-@@@01@, con-
nect communications cable across terminals 11 to 13.
SD
RD
RS-232C
SG
E5AN/EN-@@@01@
E5AN/EN
RS-232C
No.
2
11
3
12
4
13
5
6
7
20
1
• A 1:1 connection is used. The maximum cable length is 15 m. To extend
the transmission path, use the OMRON Z3R RS-232C Optical Interface.
• Use AWG24 (cross-sectional area: 0.205 mm
tional area: 2.081 mm
• Connect terminals 11 and 12 when using the E5CN-@@PH as the exter-
nal power supply for the ES1B.
• Connect terminals 14 and 15 when using the E5CN-@@PB as the exter-
nal power supply for the ES1B.
• Connect terminals 14 and 15 when using the E5AN/EN-@@P as the
external power supply for the ES1B.
E5CN-@@PH
11
12
• The following table provides the specifications of the external power sup-
ply for ES1B.
Output voltage
Output current
Host computer (DOS/V)
RS-232C: 9-pin
RD (RXD)
2
SD
SD (TXD)
3
RD
ER (DTR)
4
SG
SG
5
6
DR (DSR)
RS (RTS)
7
8
CS (CTS)
2
) shielded twisted-pair cable.
Cross-sectional area of
conductor
AWG24: 0.205 mm
AWG14: 2.081 mm
E5CN-@@PB
(+)
14
(+)
( )
( )
15
12 VDC 10%
20 mA max.
Section 2-2
E5AN/EN
RS-232C
No.
11
SD
12
RD
13
SG
2
) to AWG14 (cross-sec-
2
2
E5AN/EN-@@P
14
(+)
( )
15