Operation Level
lcr2
Leakage Current 2 Monitor
Function
Monitor
See
See
prst
Program Start
Function
Operation
See
See
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
This parameter measures and displays the heater current value.
• HS are not detected if the control output (heating) OFF time is 190 ms or
less.
Monitor range
0.0 to 55.0
• ffff is displayed when 55.0 A is exceeded.
• If an SSR short-circuit is detected, the HA indicator will light, and the rela-
tive setting level will flash on the No. 1 display.
■ Related Parameters
Hs alarm 1, HS alarm 2 (adjustment level): Page 135
HS alarm use (advanced function setting level): Page 174
Error Displays lcr2: Page 206
This parameter starts and stops the simple program function.
• The RUN/STOP status will automatically switch to RUN when this param-
eter is set to STRT.
• The simple program will stop when this parameter is set to RSET.
• This parameter will function as a monitor display for the start/stop status
of the simple program if an event input is selected to start the simple pro-
gram.
Setting range
RSET
Stops the simpler program.
STRT
Starts the simpler program.
■ Related Parameters
Soak time remain: Page 124, RUN/STOP: Page 124 (operation level)
Soak time, Wait band (adjustment level): Page 141
Program pattern (initial setting level): Page 151
Soak time unit (advanced function setting level): Page 181
Heater burnout and HS alarms must
be supported (two CTs).
Alarm 1 must be assigned.
The "HS alarm use" parameter must
be set to ON.
Unit
A
The "program pattern" parameter
must not be set to OFF.
Default
rset
Section 5-3
123