Wiring Terminals
CT Inputs
14
CT
15
E5CN-@@H@
Event Inputs
ALM2
ALM1, HBA/HS alarm,
input error
E5CN
ALM3
ALM2
ALM1, HBA/HS alarm,
E5AN/EN
• The relay specifications are as follows:
E5CN/CN-U
SPST-NO 250 VAC 1 A
E5AN/EN
SPST-NO 250 VAC 3 A
• When the HBA or the HS alarm is to be used with the E5CN-@@H@ or the
E5CN-@@HH@, connect a current transformer (CT) across terminals 14
and 15 or terminals 13 and 15 (no polarity).
• When the HBA or the HS alarm is to be used with the E5AN/EN-@@H@
or E5AN/EN-@@HH@, connect a current transformer (CT) across termi-
nals 14 and 15 or terminals 15 and 19 (no polarity).
13
14
CT2
CT1
15
E5CN-@@HH@
• When event inputs are to be used with the E5@N-@@@B, connect to ter-
minals 11 to 13.
11
12
EV1
EV2
13
E5CN-@@@B
• Use event inputs under the following conditions:
• The outflow current is approximately 7 mA.
Contact input
ON: 1 k max., OFF: 100 k min.
No-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current
0.1 mA max.
Polarities during no-contact input are as follows:
ALM1, input error
ALM2
E5CN-U
input error
CT
E5AN/EN-@@H@
EV1
EV2
E5AN/EN-@@@B
Section 2-2
CT1
CT2
E5AN/EN-@@HH@
27