Settings (Hs Alarm) - Omron E5CN User Manual

Digital temperature controller
Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Using HBA and HS Alarms
Heater burnout
hb1
detection 1
0.0
hb1
2.5

3-10-6 Settings (HS Alarm)

Operating Procedure
Operation Level
PV/SP
C
25
100
Initial Setting Level
Input type
in-t
5
Initial Setting Level
Moves to ad-
amov
vanced function
setting level
-169
Advanced Function Setting Level
init
off
HS alarm
hsu
use
on
62
8. Select the "heater burnout detection 1" parameter by pressing the M key.
Refer to 3-10-3 Calculating Detection Current Values on page 56 when
making the settings.
9. For this example, set 2.5. To return to the operation level, press the O
key for less than one second.
To activate the HS alarm, set the "HS alarm use" parameter to ON in the
advanced function setting level and set the "HS alarm 1" and "HS alarm 2"
parameters in the adjustment level.
This procedure sets the "HS alarm 1" parameter to 2.5.
Moving to the Advanced Function Setting Level
The "HS alarm use" parameter setting is already ON by default, so set the "HS
alarm 1" parameter.
1. Move to the advanced function setting level.
Press the O key for at least three seconds to move from the operation
level to the initial setting level.
2. Select "move to advanced function setting level" by pressing the M key.
3. Press the D key to enter the password ( 169), and move from the initial
setting level to the advanced function setting level.
The top parameter in the advanced function setting level is displayed.
4. Select the "HS alarm use" parameter by pressing the M key.
Check that this parameter is set to ON (the default).
Next, set the "leakage current 1 monitor" parameter.